The temperature data of transformer A, B, C and iron core are monitored and displayed in real time by high reliable and high precision double-loop temperature sensor. And has 4 4 ~ 20mA current loop synchronous output function; 485 communication remote background monitoring; Tripping or alarm contact can also be started when the transformer overtemperature occurs; In addition, the device also supports fan disconnection alarm, box open alarm and "black box" intelligent data storage and other functions.
External dimension of device

| 
			 Model  | 
			
			 Way to install  | 
			
			 Appearance dimension (long X high X deep)  | 
			
			 Open hole size (long, X-wide)  | 
			
			 Weight  | 
		
| 
			 BW-8601  | 
			
			 Embedded, bracket  | 
			
			 160X180X187mm  | 
			
			 151.5X75.5mm  | 
			
			 0.95kg  | 
		
| 
			 BW-8602  | 
			
			 Embedded, bracket  | 
			
			 200X260X95mm  | 
			
			 231X181mm  | 
			
			 2.13kg  | 
		
● Single or double groups of the same or different temperature sensor, accurate temperature measurement, reliable action;
● Supports up to 4 channels of 4 ~ 20mA synchronous output;
● The capacity of overtemperature alarm and trip relay is optional, up to AC250V/8A or DC220V/5A;
● "Black box" intelligent record data, data is safer, fault time information perfect reproduction;
● Fan fault disconnection alarm, intelligent judgment fan circuit is normal;
● Double open signal input, support box open alarm, support custom;
● All parameters can be set by menu, friendly man-machine interface.
Main technical parameters of the product
● Power supply: AC220V
Low power consumption: < 15 w
● Resolution: 0.1℃
● Measuring temperature range: 0-200℃
● Ambient temperature: -10~+5℃, relative humidity <90%RH
● Control parameter setting: all parameters can be set by menu
● Sensor wiring mode: three line system
● Control and signal output:
Fan control: double contact passive contact output, single contact capacity AC250V/8A. Overtemperature alarm: passive contact output, default AC250V/8A, can be customized to DC220V/5A.
Overtemperature trip: passive contact output, default AC250V/8A, can be customized to DC220V/5A.
Fault alarm: passive contact output, AC250V/5A.
● Communication port: RS485 or RS232.


+86-312-5907779
                  
Home
Tel
Product